Click here to make tpub.com your Home Page

Page Title: Facility Control Room
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home

   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 



DOE-HDBK-3010-94
Appendix B; Production Support Lab
3.1.5.8 F acility C on trol R oom
The H-7 facility does not have a designated control room. Remote alarms for the air
sampling system, fire detection and suppression, ventilation pressure, etc. are available in the
utility room, which has designated shift operators to detect an alarm at the panel or via the
remote indicator horns spaced throughout the utility room. Ventilation system controller
status readout and remote controls are available by the alarm panel as well and are logged
hourly.
3.1.5.9 E lectrical P ow er D istrib u tion
The H-7 facility is provided with split bus redundant normal power, auxiliary power from the
facility diesel, and critical indication power from uninterruptable power supplies (UPS).
Normal power is received from two separate public utilities. Utility A provides power to
one main bus via the 32 substation, while Utility B provides power to the other main bus via
the 33 substation. Automatic transfer switches will connect a given bus to the other
substation upon loss of power from one supplier.
Auxiliary power is provided to the facility by a 250-kw diesel generator located in its own
compartment in the utility area. Loss of power from both normal sources will automatically
start the diesel and commence a timing sequence that will transfer emergency busses to the
diesel once it is running at rated speed. Typical time for power restoration is on the order of
10 seconds. Upon restoration of power, the ventilation fans will automatically restart in the
appropriate sequence.
There are two separate UPS in the H-7 facility. The first is dedicated to the criticality alarm
systems and provides operational power for up to 3 hours. The second UPS provides power
to the air sampling system and the ventilation readout panel for approximately 1.5 hours.
The building grounding system serves two functions. As the building electrical ground, it
offers a path to ground for electrical faults, providing additional protection along with
breakers and fuse blocks and allowing "bleedoff" of static electrical charges. Its second
function is to provide a "bleedoff" path to ground in the event lightening strikes the building.
3.1.5.10 Instru m en t A ir
Instrument air is generated by a small compressor unit in the utility room. It provides air for
a variety of small users, the most significant being the automatically controlled dampers on
the ventilation system. These units fail in their current position upon loss of instrument air.
Page B-90


Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business