4. 120/240-V, three-phase, four-wire, delta. (Midpoint of one phase used as a
grounded circuit conductor.)
The following systems are not required to be solidly grounded:
1. 240-V, three-phase, three-wire, delta
2. 480-V, three-phase, three-wire
3. 600-V, three-phase, three-wire.
These electrical systems do not supply phase to neutral loads. They supply only phase-to-phase
loads.
Transformer secondary
1φ, Wire
1φ, 3 Wire
120 V
120/240 V
(Neutral)
Grounded conductor
Transformer
secondary
3φ, 4 W
120/208 V
277/480 V
120/240 V
and
1φ, 208 V
(Neutral)
Grounded conductor
Transformer secondary
corner ground
3φ, 3 W
240 V
480 V
Grounded conductor
(Not a neutral)
NEC Section 250-5 (b)
OSHA Section 29 CFR 1910.304 (f) (1) (iv)
Figure 4-5. Systems of 50 to 1,000 V AC that operate grounded are required to have the grounded conductor
connected to earth ground at the supplying transformer and service equipment.