Click here to make tpub.com your Home Page

Page Title: Figure 4-6. The grounded (neutral) conductor is used to carry normal neutral current or ground fault current
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home

   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 



DOE-HDBK-1092-98
NEC Section 250-23 (b)
OSHA Section 29 CFR 1910.304 (f) (4)
Figure 4-6. The grounded (neutral) conductor is used to carry normal neutral current or ground fault current
in case a ground fault should develop on one of the ungrounded (hot) phase conductors.
Step 1:
Service exceeding 1100 kcmil--NEC Table 250-94 2400 kcmil x 0.125 = 300
kcmil
Answer:
The grounded conductor is required to be at least a #300 kcmil, THWN copper
conductor.
This method is used where the service entrance conductors are over 1100-kcmil copper or
1750-kcmil aluminum. NEC Table 250-94 cannot be used for sizing the grounded conductor. The
grounded conductor is required to be not less than 12 1/2% of the cross-sectional area of the largest
phase conductor.
Note: NEC Table 250-94 is used only if the service conductors are rated less than 1100 kcmil for
copper or 1750 kcmil for aluminum.
4-13


Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business