DOE-HDBK-1092-98
To be acceptable for installation and use, utilization equipment will be listed or labeled by a
NRTL.
Utilization equipment that is not listed or labeled will meet one of the requirements of 29 CFR
1910.399, Acceptable, (i)(ii), or (iii).
Utilization equipment that is not listed or labeled will be examined, accepted, and documented
by a qualified person.
Utilization equipment must be used in accordance with its listing and labeling requirements.
NOTE: Utilization equipment includes laboratory and shop equipment, appliances, or other
devices that operate from an electrical energy source.
5.6.6
TEST INSTRUMENTS AND EQUIPMENT
Test instruments and equipment are intended only for use by qualified personnel and shall be used
in accordance with 29 CFR 1910.334(c). In addition, a qualified person will inspect all test
instruments and equipment to ensure that it is safe to use as intended by the manufacturer. If found
unsafe, they will not be used unless warning labels, special operating procedures, or modifications
are used to mitigate the hazard.
Test instruments and equipment will be visually inspected before each use.
Test instruments and equipment and their accessories shall be electrically rated for their
intended use.
5.6.7
EQUIPMENT OF FOREIGN MANUFACTURE
All equipment of foreign manufacture is subject to acceptance as defined in 29 CFR 1910.399.
Listing and labeling of equipment by foreign laboratories or standards may require examination to
ensure that the equipment is wired to the electrical requirements of NFPA 70 as well as 29 CFR
1910.334.
5.6.8
APPLIANCES FOR PERSONAL USE
All appliances for personal use in the workplace such as coffee pots, refrigerators, and radios should
be listed and exhibit the label of a NRTL.
5.6.9
QUALIFIED EXAMINERS OF RESEARCH AND DEVELOPMENT
(R&D) EQUIPMENT
R&D managers may appoint at least one person in their organization to examine equipment and
materials for approval prior to use. This person(s) will be knowledgeable in specified code and
regulation requirements for examination and with the NRTL process. This person will contact an
electrical safety staff member for guidance in examination procedures.
NOTE: If an organization does not have a qualified person, an electrical safety staff member should
be contacted for assistance.