Click here to make tpub.com your Home Page

Page Title: Conductors
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home

   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 



DOE-HDBK-1092-2004
cannot under any conditions exceed 8 mA, or for dc voltage if the current cannot, under any
circumstances, exceed 30 mA.
6.3.2.2 CONDUCTORS
Hoistway door conductors from the door interlocks to the hoistway riser shall be flame retardant,
suitable for a temperature of at least 200C, and Type SF or equivalent. See NEC Table 400.4
of the NEC for approved types of elevator cables and Note 5 to NEC Table 400.4 concerning
special requirements for traveling control and signal cables. Operating control and signal cable
conductors may be as small as #24 AWG. Traveling cable conductors must be #20 AWG or
larger.
6.3.2.3 DISCONNECTING MEANS
The disconnecting means requirements for elevators and escalators are both specific and
extensive, requiring careful study of the codes and installation plans during design, acceptance
testing, and routine inspections. Some of the basic requirements of NEC 620.51 are the
following:
1. There shall be a single means of disconnecting all ungrounded conductors to the main
power supply of each unit.
2. A single elevator or escalator, with multiple driving machines, shall have one disconnecting
means to disconnect the motors and control valve operating magnets.
3. When there is more than one driving machine in a machine room, the disconnecting means
shall be labeled.
4. The disconnect shall be a fused motor circuit switch or circuit breaker capable of being
locked open.
5. The disconnect shall not be provided with a means of being operated from a remote
location.
6. A circuit breaker disconnecting means shall not be opened automatically by a fire alarm
system, except as allowed by NEC.
7. The within-sight rule applies to all elevator equipment disconnects. Specific locations are
given for elevators with or without field control.
8. The disconnecting means shall be installed in a location that is readily accessible to only
qualified persons.
When power from more than one source is used for single- or multiple-car installations, a
separate disconnect should be provided for each source. These disconnects should be in sight
of the equipment supplied, and warning signs should be placed on or adjacent to the disconnect
to read. For example, "Warning: Parts of the control panel are not deenergized by this switch."
Lighting circuits for each elevator require a disconnect switch in the equipment room labeled for
the car it serves and lockable in the open position.
6-8


Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business