Click here to make tpub.com your Home Page

Page Title: Figure 4-6. The grounded (neutral) conductor is used to carry normal neutral current
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home

   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 



DOE-HDBK-1092-2004
NEC 250.24(b)
Figure 4-6. The grounded (neutral) conductor is used to carry normal neutral current
or ground fault current in case a ground fault should develop on one of the
ungrounded (hot) phase conductors.
NEC 250.24 lists the rules for sizing the grounded conductor where it is not used as a grounded
neutral circuit. NEC gives the rules for calculating and sizing the grounded conductor when it is
used as a circuit conductor. The minimum size for the grounded conductor is computed as
follows:
1.
The basic rule is to select the size directly from NEC Table 250.66 when the size of the
service-entrance conductors is not larger than 1100 kcmil copper or 1750 kcmil aluminum.
2.
When the service entrance conductors are larger than 1100 kcmil copper or 1750 kcmil
aluminum, the grounded conductor shall be 12 percent of the largest phase conductor.
3.
Where the service phase conductors are paralleled, the size of the grounded conductor
shall be based on the total cross-sectional area of the phase conductors.
For example: What size THWN copper grounded conductor is required for a service having a
total kcmil rating of 250 per phase? (All phase conductors are THWN copper)
Step 1:
Service less than 1100 kcmil - NEC Table 250.66, 250 kcmil requires #2
copper
Answer: The size of the grounded conductor is at least #2 THWN copper.
4-11


Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business