Click here to make tpub.com your Home Page

Page Title: Inspection and Records
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home

   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 



DOE-HDBK-1092-2004
6.3.6
INSPECTIONS AND RECORDS
Elevator inspections and recordkeeping are performed in accordance with the local authority
having jurisdiction. The ANSI/ASME A17.2 series of inspectors manuals provide a guide for
performing tests and inspections as well as recommended inspection checklists. In addition to
acceptance inspections and tests, the code requires 1- and 5-year inspections for electric
elevators and 1- and 3-year inspections for hydraulic elevators.
6.3.6.1 CODES
Elevators are required to be in compliance with the issue of ANSI/ASME A17.1 in force the date
they were installed. If the local authority has adopted ANSI/ASME A17.3, the code for existing
installations, they shall be in compliance with it, except they shall not be downgraded to it. When
ANSI/ASME A17.3 is in force, it becomes the minimum standard to which installations shall
adhere, and if existing installations are upgraded in accordance with ANSI/ASME A17.1, Part
XII, they shall also be in compliance with the more stringent requirements of A17.3.
6.3.6.2 INSPECTOR QUALIFICATIONS
Inspectors should meet the requirements of ANSI/ASME QEI-1 and be recognized by the local
enforcing authority. Repair and maintenance personnel should be qualified elevator mechanics.
6.4
PORTABLE AND VEHICLE-MOUNTED GENERATORS
Using portable and vehicle-mounted generators to operate electric tools on job sites is permitted
under specific conditions.
However, OSHA inspections have disclosed a potentially serious hazard resulting from the use
of portable generators. Both OSHA and the NEC permit the use of two-wire, single-phase
generators of not more than 5,000 W "where the circuit conductors of the generator are
insulated from the generator frame and all other grounded surfaces." Under these conditions,
neither the receptacles, cord sets, nor tools need to be protected by GFCIs or an assured
equipment grounding conductor program. This exception from using GFCIs is granted because
with an insulated (isolated) circuit, there is no dangerous current flow from the generator-fed
conductors to ground, structural steel, or any other grounded object. However, the use of GFCI
devices is still recommended.
If the circuit conductors are not isolated, however, the shock hazard would be the same as with
any other electrical source and the exemption does not apply. In wet or high humidity
environments, circuit conductors may not be suitably isolated and the exception would not
apply.
All portable electric generators that supply 15-or 20-A, 120-V receptacles and that are in use or
are available for use on construction sites shall meet all the following conditions or be used only
with either GFCIs or an assured equipment grounding conductor program.
1. They must be rated not more than 5 kW.
2. They shall have only a two-wire circuit (i.e., only 120-V output).
6-11


Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business