Click here to make tpub.com your Home Page

Page Title: Output voltage
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home

   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 



DOE-SPEC-3021-97
The inrush characteristics must come from an analysis of the loads themselves.
********************
Output voltage. The UPS inverter shall maintain the output voltage
3.3.2.1
within +[  ] and -[  ]% and output frequency within +[  ] and
-[  ]%, when delivering no load, through rated continuous output of
[  ] kVA at [  ] pf lagging through unity pf with steady-state variation
in normal supply voltage and frequency as specified in paragraph
3.2.1 in any combination, or with variations in the dc power supply
voltage as specified in paragraph 3.3.4.
3.3.2.2
Transient response. Upon sudden application or removal of [  ]%
load in one step, the transient response of the UPS systems (with
transfer switch) shall not permit the voltage to deviate simultaneously
more than +[  ]% (on peak-to-peak measurement basis) and it shall
recover to within +[  ]% of nominal voltage in less than [  ] cycles.
Frequency shall remain within the steady state requirements at all
times (paragraph 3.3.2.1 above).
Harmonic content. The total harmonic content of the UPS inverter
3.3.2.3
output shall be less than [  ]% rms. The content of any single
harmonic shall be less than [  ]% rms.
3.3.2.4
Inrush. The inverter shall tolerate a maximum expected inrush of
[  ] kVA for a duration of [  ] milliseconds at rated voltage and at
[  ] lagging power factor.
ATTENTION:
The term "thermal degradation" means that no components within the system shall suffer any change in
performance due to the worst case operating temperatures in the system while the system is operating within
specified limits.
********************
3.3.2.5
Operating constraints. The UPS system shall operate continuously
within the specified voltage and frequency limits, from no-load to
full-load conditions without thermal degradation. The UPS system
inverter shall operate within its specified output boundaries when
supplying the inrush load by transferring the inrush demand, if
required, to the internal bypass ac power source through operation
of the transfer switch.
3.3.2.6
Synchronization.
a. The UPS system inverter output shall be frequency and phase
synchronized to the internal bypass source frequency (as
indicated in subparagraph b. below). In the event the Owner's
electrical distribution system frequency is outside the limits given
in paragraph 3.2.1, the inverter shall revert to its own internal
standard which shall maintain the output frequency
12


Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business