are met, the resulting analysis should significantly contribute to the analysis required under the
DOE-STD-1027-92 (CH-1) for release mechanisms. However, analyses beyond PSM Rule
requirements may be needed to comply with other SAR requirements for Nuclear Hazard
Category 2 Facilities.
NUCLEAR HAZARD CATEGORY 1 FACILITIES.
Fault tree/event tree analyses are required if the
facility is a large reactor. If the facility is not a reactor and a PSM Rule PrHA is required, the
analyses can be conducted as described for Nuclear Hazard Category 2 Facilities. Different
systems or processes within the facility may be analyzed using different methods. For example,
HAZOP studies may be used as the PrHA method for processes that contain chemical hazards.
Fault tree/event tree analyses may be used to analyze systems that do not need to comply with
the PSM Rule.
All documents required by the PSM Rule should be referenced and their significant findings
summarized in the SAR. References and summaries should include not only the results of the
PrHA, but also all documents concerning the resolution of the PrHA team's findings.