|
| DOE-STD-1128-98
Guide of Good Practices for Occupational Radiological Protection in Plutonium Facilities
C.5.2 Electrical Power
Both normal and emergency power supplies should be available to a plutonium facility to
ensure that critical systems can continue to operate under both normal and accident
conditions.
C.5.2.1 Normal Power
A plutonium facility's normal electrical power needs should be met by two primary
feeders. The preferred primary feeder should provide basic service to the facility
and consist of a radial feeder connected directly to the main substation serving the
area. To minimize power outages, this feeder should be an express feeder and
should not have any other loads connected to it.
The alternate primary feeder should be in ready standby to provide backup power
to the preferred primary feeder power supply. In the event of a forced outage or
planned maintenance of the preferred primary feeder, the power load should
automatically transfer to the alternate feeder. The alternate primary feeder should
also be a radial feeder connected directly to a substation and should have no other
loads connected to it. To minimize simultaneous outages of the preferred and
alternate primary feeders due to lightning or other physical damage, the two feeders
should have maximum physical separation.
C.5.2.2 Emergency Power
The facility should be provided with a reliable, local source of emergency power if
both primary sources fail. The emergency power source should be completely
independent of the preferred and alternate primary feeders. The emergency power
should be generated onsite by turbines or diesel generators with automatic starting
and switch-over equipment. The emergency system should be physically separated
from the normal power systems, except at the automatic transfer switch, so that any
electrical or mechanical breakdown of the normal power system will not render the
emergency system inoperative.
The time lag between electrical power failure and the resumption of emergency
power should not exceed 20 seconds, and the emergency system should remain
energized for at least 5 minutes after the restoration of primary power to allow for
an orderly transition. The emergency power sources should have sufficient
capacity and sufficient fuel supplies stored onsite to maintain the integrity of all
critical building systems for approximately 48 hours. The amount of time that
emergency power is necessary should be determined by the requirements for
bringing the processes to safe shutdown condition. Chemical and thermal inertia
also should be considered. The emergency power system should be able to carry
identified critical loads such as air exhaust and supply systems, fire-detection and
fire-suppression systems, related instrumentation and control functions, necessary
criticality and radiation-monitoring instrumentation, certain processing equipment,
and any other essential building systems identified during safety analysis.
Sensitive safety equipment should be tested to verify that it will remain operable
during the switch-over and after enduring the electrical transient.
C-25
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |