| DOE-HDBK-1139/3-2005
Sources11
Consolidated Requirements12
4.5.6.2 Complete removal of the stem from a
29CFR1910.253(b)(5)(ii)(R)
diaphragm-type cylinder valve shall be
(3)
avoided.
[NOTE: Stems may be removed before
cylinder disposal.]
4.5.7
When compressed gas cylinders are not in use or are
ANSI Z-49.1, 10.8.4.10;
empty, their valves shall be closed.
CGA G-1, 5.3.3.11;
CGA G-1, 4.2.11;
29CFR1910.253(b)(2)(ii);
29CFR1910.253(b)(2)(iii);
29CFR1910.253(b)(5)(ii)(G);
29CFR1910.253(b)(5)(ii)(H);
29CFR1926.350(a)(8)
4.5.8
Where cylinders are designed to accept valve
ANSI Z-49.1, 10.8.3.6;
protection caps, caps shall be in place and hand tight at
all times except when connected for use.
CGA G-1, 5.1.9;
CGA G-1, 5.5.1;
CGA P-1, 3.4.1;
NFPA 55, 7.1.4.2;
29CFR1910.253(b)(2)(iv);
29CFR1910.253(b)(5)(ii)(A);
29CFR1926.350(a)(1)
4.5.9
Where valve outlet caps and/or plugs are provided by
CGA P-1, 3.4.2;
the manufacturer, the user shall keep the device on the
valve outlet at all times except when secured and
NFPA 55, 7.1.4.3.1
connected for use.
4.5.9.2 Valve outlet caps and/or plugs shall be in place
CGA G-1, 5.5.1;
and tightened before shipment of the cylinder
CGA P-1, 3.4.3
back to the supplier.
4.5.10 Pry bars shall not be used under valves or valve
ANSI Z-49.1, 10.8.3.2;
protection caps to pry cylinders loose when frozen or
otherwise affixed to the ground.
29CFR1910.253(b)(5)(ii)(C);
29CFR1926.350(a)(5)
4.5.10.1 Warm, not boiling water shall be used to
29CFR1926.350(a)(5)
thaw cylinders loose.
53
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |