| DOE-STD-1120-2005/Vol. 2
cause and develop an approach to bring the exposures to ALARA. The results of the investigation
indicated that the building HVAC system contributed to the formation of fugitive dust by allowing
contamination to be continually resuspended. Three alternatives were proposed to correct this situation:
(1) discontinue activities within the area; (2) have workers wear respiratory protection equipment while
performing work within the area; and (3) the preferred alternative of reducing the forced air into the area
by installing an in-line damper. Option three was implemented and the CAM within the area was
monitored closely for the next two weeks and was found to be within expected acceptable values.