| DOE-STD-3020-2005
TABLE 5.5
AXIAL FLOW RECTANGULAR HEPA FILTERS WITH INLET/OUTLET
CONNECTIONS(S) - NOMINAL SIZES AND RATINGS
(Note1)
Size
Maximum Rated Air Flow
Maximum Resistance (Note
(Note 2)
(Note 4)
3)
(m3/hr)
(Inches)
(mm)
(ACFM)
In wg
Pa
8 x 8 x 10
203 x 203 x 254
80
136
1.3
325
12 x 12 x 12
305 x 305 x 305
125
212
1.3
325
12 x 12 x 16
305 x 305 x 406
250
425
1.3
325
24 x 24 x 12
610 x 610 x 305
500
850
1.3
325
24 x 24 x 16
610 x 610 x 406
1000
1700
1.3
325
Notes:
1. Reprinted from ASME AG-1, by permission of the American Society of Mechanical
Engineers. All rights reserved.
2. Dimensions are height by width by depth. Depth includes the casing only and does not
include the length of the nipple connection(s).
3. Maximum resistance shall be as measured in ASME AG-1, FK-5621.
4. Rated airflow in ACFM is based on tests performed indoors at atmospheric pressure
close to sea level. The temperature and pressure under which the tests have been
conducted are to be recorded but are not to be used to correct rated flow.
15
|