7.0 Application Examples; Production Support Lab Example
For the sake of simplicity, the MARs are the maximum listed in Table C-2,
"Production Support Lab Facility Hazard Identification." The specific releases by lab
room are:
Liquid Sampling Room 1
Liquid
150 g * 1.0 * 2E-3 * 1.0
= 0.3 g
Waste
20 g * 1.0 * 5E-4 * 1.0
= 0.01 g
Total
0.3 g
Liquid Sampling Room 2
Liquid
150 g * 1.0 * 2E-3 * 1.0
= 0.3 g
Waste
20 g * 1.0 * 5E-4 * 1.0
= 0.01 g
Total
0.3 g
Solid Sampling Room
Liquid
120 g * 1.0 * 2E-3 * 1.0
= 0.24 g
Metal
150 g * 1.0 * 5E-4 * 0.5
= 0.04
20 g * 1.0 * 5E-4 * 1.0
= 0.01 g
Waste
Total
0.3 g
Emission Spectroscopy
Metal
250 g * 1.0 * 5E-4 * 0.5
= 0.06 g
Waste
20 g * 1.0 * 5E-4 * 1.0
= 0.01 g
Total
0.07 g
Mass Spectrometry
Liquid
120 g * 1.0 * 2E-3 * 1.0
= 0.24 g
Waste
20 g * 1.0 * 5E-4 * 1.0
= 0.01 g
Total
0.25 g
Page 7-76