Click here to make tpub.com your Home Page

Page Title: Electrical Power Distribution
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home

   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 



DOE-HDBK-3010-94
Appendix B; Plutonium Recovery Facility
The ventilation system (e.g., ventilation sequencer, differential pressure readouts, damper
positions) is monitored in the control room as well. Unlike process controls, however, the
ventilation system is also operated from the control room via an installed control panel.
Significant parameters and alarms for support buildings, such as the H-8 Liquid Waste
Treatment Facility receipt tank levels, are also provided in the control room. One of two
primary facility announcing system controls is located here as well.
2.1.5.10 E lectrical P ow er D istrib u tion
H Plant is provided with split bus redundant normal power, auxiliary power from the plant
diesel, and safe shutdown power from uninterruptable power supplies (UPS). Normal power
is received from two separate public utilities. Utility A provides power to one main bus via
the 32 substation, while Utility B provides power to the other main bus via the 33 substation.
Automatic transfer switches will connect a given bus to the other substation upon loss of
power from one supplier.
Auxiliary power is provided to the facility by a 850- kw diesel generator located adjacent to
the main building in H-3 B. This small building is constructed in a manner identical to the
main building. Loss of power from both normal sources will automatically start the diesel
and commence a timing sequence that will transfer auxiliary busses to the diesel once it is
running at rated speed. Typical time for power restoration is on the order of 10 seconds.
Upon restoration of power, the ventilation fans will automatically restart in the appropriate
sequence.
There are three separate UPS in H Plant. The first is dedicated to the criticality alarm
system and will provide operational power to the criticality alarm system for up to 3 hours.
The second UPS provides power to the air sampling system and local glovebox control
panels for approximately 1 hour. The final UPS supplies the facility control room for
approximately 0.5 hours.
The building grounding system serves two functions. As the building electrical ground, it
offers a path to ground for electrical faults, providing additional protection along with
breakers and fuse blocks and allowing "bleedoff" of static electrical charges. Its second
function is to provide a "bleedoff" path to ground in the event lightening strikes the building.
2.1.5.11 P rocess an d Instru m en t A ir
Process and instrument air represent two branches of flow from a single source. Filtered air
is drawn into one of two air compressors (on-line and standby units) rated for 300 scfm and
125 psig discharge pressure. The compressor outlet passes through drying towers to one of
Page B-18


Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business