|
| DOE-HDBK-1092-98
7.5.3.2 APPROVED CAPACITY
Grounding cables shall accommodate the maximum fault current to which the cable or equipment
might be subjected.
7.5.3.3 GROUNDING CABLES AND HARDWARE
Personal protective grounding cables consist of appropriate lengths of suitable copper grounding
cable, with electrically and mechanically compatible ferrules and clamps at each end. In addition,
appropriate hotsticks are required for installing and removing the conductor-end clamps to the
conductors. Hotsticks are required for attaching ground-end clamps if the grounded system and the
worker are at different potentials. Cluster bars provide a low-resistance means of connecting the
ground-end clamps. Each of these components will be discussed in the following subsections.
7.5.3.4 GROUNDING CABLES
Most of the grounding cables in use today (and available for purchase) are actually manufactured for
another purpose-principally as welding cable. These extra-flexible copper cables with jackets are
manufactured according to appropriate ASTM standards for both cables and jackets, and can be
expected to perform satisfactorily as grounding cables.
7.5.3.4.1 STRANDING
There are several classes of flexible cable with various stranding in the sizes normally used for
grounding cables.
7.5.3.4.2 JACKETS
Welding cables are nominally insulated at 600 volts. When used as grounding cable, the insulation
or jacket serves primarily for mechanical protection of the conductor. The flexible elastomer or
thermoplastic jackets are manufactured, applied, and tested according to ASTM standards. Black,
red, and yellow jackets are usually neoprene rubber compounds, while clear jackets are ultraviolet-
inhibited polyvinyl chloride (PVC). All jackets should have the American Wire Gage (AWG) size
stamped or printed repeatedly along the length of the cable. The clear jacket allows easy visual
inspection of the conductor for strand breakage, but becomes stiff and hard to handle at low
temperatures. The clear jacket will split or shatter at very low temperatures.
7.5.3.4.3 FERRULES
Ferrules should be threaded-stud copper base compression type. Ferrules should have the filler
compound vent hole at the bottom of the cable so that employees can visually check that the cable
is fully inserted into the ferrule. Compound should be used with crimped ferrules. The ferrules should
be crimped with the ferrule manufacturer's recommended die. The press shall have enough pressure
to completely close the die. The area covering the inserted cable jacket should not be compressed.
Heat shrink or springs should be installed over a portion of the ferrule to minimize strand breakage
caused by bending. In all cases, the manufacturer's recommendations should be followed.
7-14
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |