4.4 BONDING 
sized and selected correctly. Bonding completes the grounding circuit so that it is continuous. If a 
ground fault occurs, the fault current will flow and open the overcurrent protection devices. The 
means of bonding shall provide the following to ensure the grounding system is intact: 
1. Provide a permanent connection, 
2. Provide a positive continuity at all times, and 
3. Provide ampacity to conduct fault current. 
See Figure 4-1 on the proper grounding of electrical systems. 
Supply 
Grounded (neutral) conductor 
carrying fault current 
Service 
equipment 
Phase 
conductor 
Overcurrent 
This equipment grounding 
Protective 
conductor provides 
Device 
equipment grounding 
This conductor 
Subpanel 
provides the 
bonding of the 
equipment 
Equipment with 
ground fault 
This grounding electrode 
provides circuit and 
system grounding 
NEC Section 250-51 
Figure 4-1. Circuit and system grounding consists of earth grounding the electrical system at the supply 
transformer and the line side of the service equipment. Equipment grounding and bonding is accomplished by 
connecting all metal enclosures and raceways together with the grounding conductors. 