4.4 BONDING
sized and selected correctly. Bonding completes the grounding circuit so that it is continuous. If a
ground fault occurs, the fault current will flow and open the overcurrent protection devices. The
means of bonding shall provide the following to ensure the grounding system is intact:
1. Provide a permanent connection,
2. Provide a positive continuity at all times, and
3. Provide ampacity to conduct fault current.
See Figure 4-1 on the proper grounding of electrical systems.
Supply
Grounded (neutral) conductor
carrying fault current
Service
equipment
Phase
conductor
Overcurrent
This equipment grounding
Protective
conductor provides
Device
equipment grounding
This conductor
Subpanel
provides the
bonding of the
equipment
Equipment with
ground fault
This grounding electrode
provides circuit and
system grounding
NEC Section 250-51
Figure 4-1. Circuit and system grounding consists of earth grounding the electrical system at the supply
transformer and the line side of the service equipment. Equipment grounding and bonding is accomplished by
connecting all metal enclosures and raceways together with the grounding conductors.
4-3
|