|
| DOE-HDBK-1092-98
3. Transformer size that permits saturation of the iron core at the operating voltage
4. Transformer unloaded or very lightly loaded.
Prevention or control of ferro-resonance may be accomplished by any of the following measures:
1. Using a wye-wye transformer connection with both neutrals grounded and tied to the system
neutral.
2. Using only phase-to-neutral (not phase-to-phase) transformer connections for single-phase
transformers.
3. Limiting length of underground cable between transformers and single-pole or poorly
synchronized three-pole switching devices.
4. If single-pole or poorly synchronized switching devices must be used, ensuring that transformer
and underground cable are loaded in excess of 2% resistive load of the transformer capacity.
5. If transformer primary is ungrounded-wye, temporarily grounding the neutrals of the
transformers being switched.
6. Installing close-coupled, high-speed, three-pole switching devices to minimize the duration
of the single-phase condition during opening and closing of the circuit.
7-28
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |