DOE-HDBK-1092-98
Power supply
Shield
common
grounding bus
(for terminating
Signal common
shields from
field sources)
Local grounding bus
DC ground
Cabinet ground
Master grounding bus
AC power ground
Distribution
system
grounding bus
Bldg. ground
Plant
grounding bus
Figure 10-9. Typical control instrumentation ground system.
7. Water column used as a charged-particle beam attenuator
8. Commercial cable tray used as a mechanical support for experimental apparatus.
10.9.2.2.2 DESIGN AND CONSTRUCTION
During design, special consideration should be given to installing interlocks and protective barriers.
Signs warning of the hazards should be posted to help prevent unsuspecting personnel from being
injured.
10.9.2.2.3 OPERATION AND MAINTENANCE
Appropriate safety procedures and training should be part of the process to qualify personnel. The
procedures should describe the methods used to promote safe work practices relating to work on
energized circuits in accordance with Sect. 2.1.2, "Considerations for Working on Energized
Systems and Equipment", Sect. 2.13, "Work Practices", and 29 CFR 1910.331-335.
10-21