| DOE-HDBK-1092-98
Utility
Service
equipment
1000 A or more OCPD
NEC 230-95
Shunt trip CB
0 to 1200 A setting
NEC 230-95 (a)
R
Clearing time
shall clear a fault
of 3000 A or more
Grounding
in 1 second
electrode
conductor
Ground fault sensor
To load
Z93 0403
NEC Section 230-95
Figure 3-1. Ground-fault protection shall be provided with 277/480-V, three-phase, four-wire services with
overcurrent protection devices of 1,000 A or more. A ground fault sensor (window) can be used to encircle
all service conductors, including the grounded conductor (neutral).
3-5
|