|
| DOE-HDBK-1092-98
NEC Section 250-50 (a)
OSHA Section 29 CFR 1910.304 (f) (3)
Figure 4-2. A grounded system is equipped with a grounded (neutral) conductor routed between the supply
transformer and the service equipment.
4.5.2 UNGROUNDED SYSTEMS
Ungrounded systems operate without a grounded conductor. In other words, none of the circuit
conductors of the electrical system are intentionally grounded to an earth ground such as a metal
water pipe, building steel, etc. The same network of equipment grounding conductors is provided for
ungrounded systems as for solidly grounded electrical systems. However, equipment grounding
conductors (EGCs) are used only to locate phase-to-ground faults and sound some type of alarm.
Therefore, a single sustained line-to-ground fault does not result in an automatic trip of the
overcurrent protection device. This is a major benefit if electrical system continuity is required or
if it would result in the shutdown of a continuous process. However, if an accidental ground fault
occurs and is allowed to flow for a substantial time, overvoltages can develop in the associated phase
conductors. Such an overvoltage situation can lead to conductor insulation damage, and while a
ground fault remains on one phase of an ungrounded system, personnel contacting one of the other
4-5
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |