| ||||||||||
| 
 
  | ![]() DOE-HDBK-1092-98 
NEC Section 250-50 (a) 
OSHA Section 29 CFR 1910.304 (f) (3) 
Figure 4-2. A grounded system is equipped with a grounded (neutral) conductor routed between the supply 
transformer and the service equipment. 
4.5.2 UNGROUNDED SYSTEMS 
Ungrounded systems operate without a grounded conductor. In other words, none of the circuit 
conductors of the electrical system are intentionally grounded to an earth ground such as a metal 
water pipe, building steel, etc. The same network of equipment grounding conductors is provided for 
ungrounded systems as for solidly grounded electrical systems. However, equipment grounding 
conductors (EGCs) are used only to locate phase-to-ground faults and sound some type of alarm. 
Therefore, a single sustained line-to-ground fault does not result in an automatic trip of the 
overcurrent protection device. This is a major benefit if electrical system continuity is required or 
if it would result in the shutdown of a continuous process. However, if an accidental ground fault 
occurs and is allowed to flow for a substantial time, overvoltages can develop in the associated phase 
conductors. Such an overvoltage situation can lead to conductor insulation damage, and while a 
ground fault remains on one phase of an ungrounded system, personnel contacting one of the other 
4-5 
 | 
| 
 
 Privacy Statement - Press Release - Copyright Information. - Contact Us  |