|
| DOE-HDBK-1092-98
NEC Section 250-23 (b)
OSHA Section 29 CFR 1910.304 (f) (4)
Figure 4-6. The grounded (neutral) conductor is used to carry normal neutral current or ground fault current
in case a ground fault should develop on one of the ungrounded (hot) phase conductors.
Step 1:
Service exceeding 1100 kcmil--NEC Table 250-94 2400 kcmil x 0.125 = 300
kcmil
Answer:
The grounded conductor is required to be at least a #300 kcmil, THWN copper
conductor.
This method is used where the service entrance conductors are over 1100-kcmil copper or
1750-kcmil aluminum. NEC Table 250-94 cannot be used for sizing the grounded conductor. The
grounded conductor is required to be not less than 12 1/2% of the cross-sectional area of the largest
phase conductor.
Note: NEC Table 250-94 is used only if the service conductors are rated less than 1100 kcmil for
copper or 1750 kcmil for aluminum.
4-13
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |