5.1.5.1 PERMANENT EQUIPMENT AND WIRING
The NEC and this section are minimum requirements for DOE facilities containing explosives.
Though the NEC does not specifically address explosives, Article 500, "Hazardous (Classified)
Locations," does establish requirements for the design and installation of electrical equipment and
wiring in locations containing combustible dusts and flammable liquids, vapors, or gases that in
general are comparably hazardous. All permanent electrical equipment and wiring in work areas
containing explosives hazards shall conform to the standards of the NEC Hazardous Locations Class
II or Class I and II (dual rated). For Class II installations, provisions should be made for easy
conversion to Class I.
5.1.5.2 HAZARDOUS LOCATIONS
NEC definitions of and requirements for hazardous locations Class I and Class II are modified as
follows for application to DOE explosives facilities:
1. Areas containing explosive dusts or explosives which may, through handling or processing,
produce dust capable of being dispersed in the atmosphere shall be regarded as Class II
Division 1 hazardous locations.
2. Areas that contain exposed explosives but where no dust hazard exists shall be regarded as
Class II Division 2 hazardous locations.