Click here to make tpub.com your Home Page

Page Title: Graund Fault Circuit Interprises
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home

   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 



DOE-HDBK-1092-98
consideration. Therefore, where there are conflicts between the mandatory requirements of the above
codes, standards, and regulations, the requirements that address the particular hazard and provide the
greater safety shall govern.
2.7 GROUND FAULT CITCUIT INTERRUPTERS
There are 2 classes of ground-fault circuit interrupters and each class has a distinct function. A Class
A ground-fault circuit interrupter trips when the current to ground has a value in the range of 4 through
6 milliamperes and is used for personnel protection. A Class A ground-fault circuit interrupter is
suitable for use in branch circuits. A Class B ground-fault circuit interrupter (commonly used as
ground fault protection for equipment) trips when the current to ground exceeds 20 milliamperes. A
Class B GFCI is not suitable for employee protection.
Ground-fault circuit protection can be used in any location, circuit, or occupancy to provide
additional protection from line-to-ground shock hazards because of the use of electric hand tools.
There are four types of GFCIs used in the industry:
1. Circuit breaker type
2. Receptacle type
3. Portable type
4. Permanently mounted type.
The condition of use determines the type of GFCI selected. For example, if an electrician or
maintenance person plugs an extension cord into a nonprotected GFCI receptacle, the easiest way to
provide GFCI protection is to utilize a portable-type GFCI.
See NEMA 280-1990, "Application Guide for Ground Fault Circuit Interrupters."
2.7.1 HOW A GFCI WORKS
See Section 4.14 for ground-fault protection of equipment. GFCIs are devices that sense when
current--even a small amount--passes to ground through any path other than the proper conductor.
When this condition exists, the GFCI quickly opens the circuit, stopping all current flow to the circuit
and to a person receiving the ground-fault shock.
Figure 2-1 shows a typical circuit arrangement of a GFCI designed to protect personnel. The
incoming two-wire circuit is connected to a two-pole, shunt-trip overload circuit breaker. The
loadside conductors pass through a differential coil onto the outgoing circuit. As long as the current
in both load wires is within specified tolerances, the circuit functions normally. If one of the
conductors comes in contact with a grounded condition or passes through a person's body to ground,
an unbalanced current is established. This unbalanced current is picked up by the differential
transformer, and a current is established through the sensing circuit to energize the shunt trip of the
overload circuit breaker and quickly open the main circuit. A fuse or circuit breaker cannot provide
this kind of protection. The fuse or circuit breaker will trip or open the circuit only if a line-to-line
or line-to-ground fault occurs that is greater than the circuit protection device rating.
2-8


Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business