|
| DOE-HDBK-1092-98
grounding electrode conductor of the system sized by NEC Table 250-94. The four types of
electrodes are as follows:
1. Metal water pipe in contact with the earth for 10 ft. or more. Interior metal water pipe beyond
5 ft. from the water entrance shall not be used as a part of the grounding electrode system or
as a conductor to interconnect those electrodes. (See NEC Section 250-81.)
2. Metal frame of the building, where effectively grounded
3. Bare #4 conductor at least 20 ft in length and near the bottom of the concrete foundation (within
2 in.), or 1/2 in. reinforcing steel or rods at least 20 ft in length (one continuous length or spliced
together)
4. Bare #2 conductor encircling building at least 2-1/2 ft. in the ground (spliced together at each
end).
The grounding electrode conductor at the service equipment can be connected to any convenient
interbonded electrodes that provide a solid, effective connection. Metal water pipe shall be
supplemented by an additional electrode, which can be any of the following electrodes:
1. A rod
2. Pipe
3. Plate
4. Building steel
5. Concrete-encased electrode.
(See Figure 4-8, which lists some of the different types of grounding electrodes.)
4.14 GROUND-FAULT PROTECTION OF EQUIPMENT
See Section 2.7 for ground fault circuit interrupters for personnel protection. An increased degree of
protection in solidly grounded systems can be achieved in providing ground-fault protection that will
shunt trip circuit protective devices when user-selected levels of ground fault or leakage current flow
are detected in electrical circuits. This is required to be installed on all solidly grounded wye services
of more than 150 V to ground but not exceeding 600 V phase-to-phase where the service
disconnecting means is rated at 1,000 A or more (See NEC Sections 215-10, 230-95, 240-13, and
Figure 3-1).
4.15 PERSONNEL PROTECTIVE GROUNDS
Personnel working on or close to deenergized lines or conductors in electrical equipment should be
protected against shock hazard and flash burns that could occur if the circuit were inadvertently
reenergized. Properly installed equipotential protective grounds can aid in lessening such hazards by
providing additional protection to personnel while they service, repair, and work on such systems.(See
Section 7.5).
4-17
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |