INDUCTIVE COLLAPSED LOOPS
Figure 10-7. Intentional returns have been installed for both the pulse power supply and the controller right
in the trays for the cables. Both loops have been reduced to small cross sections, reducing inductive coupling.
Any electromagnetic (far field) radiation being generated by the pulse power supply and its cabling will also
be reduced.
10.9.2.1.4 OPERATION AND MAINTENANCE
Before starting each operation (experiment, test, etc.) the exposed portions of the grounding system
should be visually checked for any damage and to determine that all necessary connections have been
made. If more than one operation is conducted every day, then visual checks should be performed
only at the beginning of each shift, if the grounding system will be needed during that shift. The
adequacy of the grounding system should be verified annually. It is recommended that the grounding
impedance within the equipment be maintained at 0.25 ohms or less. (See IEEE 1100).
10.9.2.2
MATERIALS USED IN AN UNCONVENTIONAL MANNER
The practice of using materials or components for purposes other than originally designed needs
special safety considerations in use, identification, personnel protection, and equipment protection.