1. Ignitable concentrations of flammable gases, liquids, or vapors can exist under normal
operating conditions;
2.
Ignitable concentrations of such gases or vapors may exist frequently because of repair or
maintenance operations or because of leakage; or
3.
Breakdown or faulty operation of equipment or processes might release ignitable
concentrations of flammable gases, liquids, or vapors and might also cause simultaneous
failure of electrical equipment.
Note: In each case, ignitable concentrations are mentioned. This means concentrations
between the lower and upper flammable or explosion limits (see Section 5.3.5 and Table 5-5).
The fine-print note to NEC 500.5(B)(1) describes a number of areas and occupancies normally
classified as Class I Division 1 locations.