|
| DOE-HDBK-1092-2004
OSHA Sections 29 CFR 1910.269 (p)(4), 1926.952 (b)
Figure 6-2. A minimum clearance of 10 ft between overhead power lines and
equipment is required for 50 kV and below while a clearance of 10 ft plus 4 in. for
every kV above 50 kV is required.
6.3
ELEVATORS AND ESCALATORS
Elevators and escalators are used to move people and elevators are also used to move
materials. Design, installation, inspection, and maintenance activities require specialized
knowledge for safe operation and use.
6.3.1
CODES AND STANDARDS
A comprehensive electrical safety program for elevators and escalators can be achieved
through the application of the correct codes and standards. All elevators are required to be
constructed, installed, and maintained in accordance with ANSI/ASME A17.1. Reference
standards include NFPA 70 (NEC) for the electrical equipment wiring and NFPA 101 (Life
Safety Code). These standards reflect the interrelated roles of electrical design, maintenance,
and fire protection in the electrical safety process.
6.3.2
DESIGN SPECIFICATIONS
The electrical designer shall provide for the installation requirements of Article 620 of the NEC
as well as the ANSI/ASME A17.1 requirements for signaling, automatic fire protection, and
emergency power as required. The manufacturer shall provide the required fire service key
switches, audible alarm devices, and internal wiring up to the terminal strips in the elevator
control panel.
6.3.2.1 VOLTAGE AND CURRENT LIMITATIONS
There shall be a 300-V limitation on all operating control and signal circuits and related
equipment, including door operators. Exceptions are permitted for 25 to 60 Hz ac if the current
6-7
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |