|
| DOE-HDBK-1092-2004
4.12 GROUNDING A SEPARATELY DERIVED SYSTEM
NEC 250.30 covers the rules for grounding separately derived systems. The system grounding
conductor for a separately derived system shall be grounded at only one point. That single
system grounding point is at the source of the separately derived system and ahead of any
system disconnecting means or overcurrent devices. Where the main system disconnecting
means is adjacent to the generator, converter, or transformer supplying a separately derived
system, the grounding connection to the system grounded conductor can be made at or ahead
of the system disconnecting means.
The preferred grounding electrode for a separately derived system is the nearest effectively
grounded structural metal member of the building or the nearest effectively grounded water
pipe. If neither is available, concrete-encased electrodes or made electrodes are permitted.
In a grounded, separately derived system, the equipment grounding conductors shall be bonded
to the system-grounded conductor and to the grounding electrode at or ahead of the main
system disconnecting means or overcurrent protection device. The equipment grounding
conductor should always be connected to the enclosure of the supply transformer, generator, or
converter.
The grounding electrode conductor, the main bonding jumper, the grounded conductor, and the
equipment grounding conductor are calculated, sized, and selected by the rules listed in
Sections 4.7 through 4.10. (See Figure 4-7.)
Figure 4-7. The grounded (neutral) conductor can be used to carry both normal neutral
current and abnormal ground fault current.
4-14
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |