|
| DOE-HDBK-1092-2004
indicators or alarms, or both, and qualified personnel are available to quickly locate and eliminate
such ground faults. Ground faults must be promptly removed or the service reliability will be
reduced. See NEC for requirements on installing a high-impedance grounding system. (See
Figure 4-4.)
NEC 250.36
Figure 4-4. A high-impedance grounding system has a high-impedance unit, installed
between the grounded (neutral) conductor and the grounding electrode conductor,
which is used to regulate fault current.
4.6
GROUNDING REQUIREMENTS
Alternating current systems of less than 50 volts shall be grounded as required in NEC.
Systems of 50 to 1,000 V should be solidly grounded as required by NEC. Systems supplying
phase-to-neutral loads shall also be solidly grounded (See Figure 4-5). The following electrical
systems are required to be solidly grounded:
1.
240/120-V, single-phase, three-wire
2.
208Y/120-V, three-phase, four-wire
3.
480Y/277-V, three-phase, four-wire
4.
2 4 0 / 1 2 0 - V , three-phase, four-wire, delta (midpoint of one phase used as a
grounded circuit conductor)
The following systems are not required to be solidly grounded:
4-6
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |