|
| DOE-HDBK-1092-2004
9.8
MARKING AND LABELING REQUIREMENTS
9.8.1
GENERAL MARKING REQUIREMENTS
For all chassis and rack cabinets (electrical, computer, power distribution, etc.), the
manufacturer's name, trademark, or other descriptive marking of the organization responsible
for the product should be identified.
Other markings for power requirements are:
1. Voltage
2. Maximum rated current in amperes
3. Wattage
4. Frequency
5. Duration
6. Duty cycle
7. Other ratings as specified in the NEC (NEC 110.21)
9.8.2
HAZARD MARKING REQUIREMENTS
All enclosures containing exposed energized circuits over 600 volts nominal should be marked
"Danger High Voltage Keep Out" with a label that is permanent. These areas shall be
accessible to authorized personnel only. The label shall be placed in a noticeable location on
the access panel to the enclosure. Mark all other hazards that are associated with the
equipment.
9.8.3
OTHER REQUIREMENTS
All equipment markings shall be of sufficient durability to withstand the environment involved
and should be large enough to read.
To obtain the correct chassis load requirements for marking and labeling, monitor individual
chassis while under load. Many chassis have components that are not energized except under
certain conditions.
A normal current draw may be a few amperes, but when the chassis is sourcing current to a
load, the current draw may be much higher. Individual loads, internal and external, may be
tabulated and added to determine the chassis current labeling requirements.
For rack cabinets with power distribution units, the outside of the rack cabinet should be labeled
with the input parameters of the power distribution system installed within it.
For rack cabinets without power distribution units the outside of the rack cabinet should be
labeled with the total current on the combined systems installed within it.
9-13
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |