DOE-HDBK-1092-2004
connected by cord and plug that are available for use or used by employees. This program shall
comply with the following minimum requirements:
1. A written description of the program, including the specific procedures adopted by the
employer, shall be available at the job site for inspection.
2. The employer shall designate one or more competent persons to implement the program.
3. Each cord set, attachment cap, plug and receptacle of cord sets, and any equipment
connected by cord and plug, except cord sets and receptacles that are fixed and not
exposed to damage, shall be visually inspected before each day's use for external defects
such as deformed or missing pins or insulation damage and for indications of possible
internal damage. Equipment found damaged or defective shall not be used until repaired.
4. The following tests shall be performed on all cord sets, receptacles that are not a part of the
permanent wiring of the building or structure, and cord-and-plug connected equipment
required to be grounded:
a. All equipment grounding conductors shall be tested for continuity and shall be electrically
continuous.
b. Each receptacle and attachment plug shall be tested for correct attachment of the
equipment grounding conductor. The equipment grounding conductor shall be
connected to its proper terminal.
5. All required tests shall be performed:
a. Before first use
b. Before equipment is returned to service following any repairs
c. Where there is evidence of damage.
d. At intervals not to exceed 3 months, except that cord sets and receptacles which are
fixed and not exposed to damage shall be tested at intervals not exceeding 6 months.
6. The employer shall not make available or permit the use by employees of any equipment
that has not met the requirements of this section.
7. Tests performed as required in this section shall be recorded. This test shall identify each
receptacle, cord set, and cord-and-plug-connected equipment that passed the test and shall
indicate the last date it was tested or the interval for which it was tested. This record shall be
kept by means of logs, color coding, or other effective means and shall be maintained until
replaced by a more current record. The record shall be made available on the job site