All electrical equipment and materials for facility wiring, and similar R&D wiring, as defined by
NFPA 70 will be approved in accordance with Article 90.7, "Examination of Equipment for
Safety," and Article 110.3, "Examination, Identification, Installation, and Use of Equipment."
5.6.5 UTILIZATION EQUIPMENT
Utilization equipment is addressed in 29 CFR 1910.302 and 303. This document makes it clear
that utilization equipment is subject to the same approval and acceptance requirements as in
Section 5.6.4 of this document.
To be acceptable for installation and use, utilization equipment will be listed or labeled by a
NRTL.
Utilization equipment that is not listed or labeled will meet one of the requirements of 29
CFR 1910.399, Acceptable, (i)(ii), or (iii).
Utilization equipment that is not listed or labeled will be examined, accepted, and
documented by a qualified person.
Utilization equipment must be used in accordance with its listing and labeling requirements.
NOTE:
Utilization equipment includes laboratory and shop equipment, appliances, or
other devices that operate from an electrical energy source.
5.6.6 TEST INSTRUMENTS AND EQUIPMENT
Test instruments and equipment are intended only for use by qualified personnel and shall be
used in accordance with 29 CFR 1910.334(c). In addition, a qualified person will inspect all test
instruments and equipment to ensure that it is safe to use as intended by the manufacturer. If
found unsafe, they will not be used unless warning labels, special operating procedures, or
modifications are used to mitigate the hazard.
Test instruments and equipment will be visually inspected before each use.
Test instruments and equipment and their accessories shall be electrically rated for their
intended use.
5.6.7 EQUIPMENT OF FOREIGN MANUFACTURE
All equipment of foreign manufacture is subject to acceptance as defined in 29 CFR 1910.399.
Listing and labeling of equipment by foreign laboratories or standards may require examination
to ensure that the equipment is wired to the electrical requirements of NFPA 70 as well as 29
CFR 1910.334.
5.6.8 APPLIANCES FOR PERSONAL USE
All appliances for personal use in the workplace such as coffee pots, refrigerators, and radios
should be listed and exhibit the label of a NRTL.