| DOE-HDBK-1139/3-2003
Sources10
Consolidated Requirements
4.2.1.1 Hazard ratings shall be assigned in accordance with
NFPA 704.
NFPA 704
4.2.1.2 Signs shall not be obscured or removed.
4.2.1.3 Signs shall prohibit smoking or an open flame within 20
ft of where toxic, pyrophoric, oxidizing, or flammable
CGA P-1, 4.2.1.5;
gases are stored.
NFPA 55, 7.1.1;
NFPA 55, 7.6.3.2;
(i)
4.2.2 Compressed gas cylinders shall be stored away from stairways,
elevators, exit routes, or gangways, in assigned places where
they will not be exposed to physical damage (for example,
CGA G-1, 4.2.4;
damage from vehicles, damage from falling ice, etc.).
CGA P-1, 3.7.3;
NFPA 55, 7.1.5.4;
NFPA 55, 7.1.5.6;
NFPA 55, 7.1.5.9;
4.2.3 Compressed gas cylinders shall be stored in an upright position
(see definition) with their valve protection caps in place and
secured to prevent cylinders from falling over or being knocked
over.
CGA P-1, 3.7.4;
[EXCEPTION: All requirements cited here indicate that upright
storage is not required for lecture bottles or cylinders used in
NFPA 55, 7.1.3.4;
self-contained breathing apparatus.]
NFPA 55, 7.2.1.2;
(ii)
4.2.4 Overhead cover for outdoor storage areas of compressed gases
shall be of non-combustible construction, open on three sides
and shall not be considered indoor storage.
4.2.4.1 Storage areas shall be kept clear of dry vegetation and
combustible materials for a minimum distance of 15 ft in
all directions.
4.2.4.2 Cylinders stored outdoors shall not be placed in direct
contact with the earth or on surfaces where water can
CGA G-1, 4.2.13;
accumulate.
28
|