| DOE-HDBK-1139/3-2003
Sources10
Consolidated Requirements
4.5.2.1 The color of the cylinder shall not be the only
CGA P-1, 3.2.5
means used to identify the gas it contains.
4.5.2.2 Labels or markings placed on compressed gas
ANSI Z49.1, 10.8.1.4 and 5;
cylinders by the manufacturer or distributor shall
not be defaced or removed.
CGA G-1, 5.1.3;
CGA P-1, 3.2.2;
NFPA 55, .7.1.2.2;
29CFR1910.253(b)(5)(ii)(L)
4.5.2.3 Cylinders not bearing a legible label or other
ANSI Z49.1, 10.8.1.4
identification shall not be used and shall be
returned to the manufacturer or distributor.
4.5.2.4 Gas name markings shall not be cut into the metal
NFPA 51, 2.1.3
of the cylinder by the user.
4.5.3 Compressed gas cylinders shall not be subjected to
CGA P-1, 3.3.3
temperature extremes.
4.5.3.1 Compressed gas cylinders shall not be exposed to
ANSI Z-49.1, 10.8.1.8;
temperatures exceeding 125F
CGA P-1, 3.3.3;
NFPA 55, 7.1.5.5;
29CFR1910.253(b)(2)(i)
4.5.3.2 Direct flames or heat shall not be applied to a
CGA P-1, 3.3.3;
compressed gas cylinder.
CGA P-1, 4.2.2;
CGA G-1, 5.1.6;
CGA G-1, 5.3.3.12;
NFPA 55, 7.1.5.7;
29CFR1926.350(b)(3)
4.5.3.2.1 Cylinders exposed to fire shall not be
CGA P-1, 3.3.6;
shipped or used until the manufacturer
or supplier requalifies them in
NFPA 55, 7.1.8
accordance with the pressure and
vessel code under which they were
manufactured.
51
|