| DOE-HDBK-1139/3-2003
Sources10
Consolidated Requirements
4.5.15 Oxygen and fuel and other compressed gas cylinders,
ANSI Z49.1, 10.3.3;
equipment, pipelines or apparatus shall not be used
ANSI Z49.1, 10.6.5;
interchangeably with any other gas and each shall be
used only for the service for which it was approved.
CGA G-1, 5.3.3.4;
CGA P-1, 3.8.7;
29CFR1910.253(3)(1);
29CFR1926.350(f)(1)
4.5.16 All connections shall be gas tight and no leaks shall be
ANSI Z49.1, 10.5.2.1;
present in the system.
CGA G-1, 5.3.3.6;
CGA P-1, 3.8.4;
NFPA 55, 7.3.1.4.1
4.5.16.1 A flame shall not be used for the detection of
ANSI Z49.1, 10.5.2.1;
leaks in compressed gas systems. Soapy
water is one acceptable method.
CGA P-1, 4.2.1.5
4.5.17 Backflow protection shall be used when the backflow
CGA P-1, 3.7.5;
of gas can result in a hazardous condition.
CGA P-1, 3.8.2;
NFPA 55, 7.3.1.4.2
4.5.18 Compressed gas systems shall be designed for their
NFPA 55, 7.3.1.2;
intended use and shall be designed by persons
NPFA 55, 7.5-7.10
competent in such design. .
[NOTE: Additional requirements for corrosive,
flammable, oxidizing, pyrophoric, toxic/highly toxic,
and unstable reactive gases can be found in NFPA 55,
7.5-7.10.]
4.5.19 Compressed gases shall never be used from cylinders or
ANSI Z49.1, 10.8.4.1;
high pressure manifolds without reducing the pressure
through a suitable regulator unless the equipment used
CGA G-1, 5.3.1;
is designed to withstand full cylinder pressure.
CGA P-1, 3.8.8;
NFPA 45, 8.1.5.2;
NFPA 51, 3-1.4;
NFPA 51, 3-2.5;
NFPA 51, 3-4.5;
29CFR1926.350(d)(3);
29CFR1910.253(b)(5)(iii)(I)
55
|