| DOE-SPEC-3018-96
c. Battery is Used in a Grounded
DC System
[Yes] [No]
] minimum [
] maximum
d. Number of Cells per Battery Jar
[
e. Grid Alloy
[Pure Lead] [Lead-Calcium]
[Lead-Antimony] [Lead-Selenium]
]
f.
Positive-Plate Construction
[Pasted plate] [
g. End-of-Duty Cycle Voltage
or Minimum Voltage During
] V/cell
Duty Cycle
[1.75] [
]
h. Specific Gravity
[1.250] [
ATTENTION:
Insert the required information in the following paragraph.
********************
3.2.1
Operating environment. Each battery and associated equipment shall meet the
performance requirements of this specification while operating under the
environmental conditions specified below.
]
a. Battery String Designation
No. [1] [
ft (
m)]
b. Elevation Above Mean Sea Level
[
c. Battery Room Ambient
Temperature Range
[70 to 80F (21 to 27C)]
to
F (
to
C)]
[
d. Battery Room Ambient Design
F (
C)]
Temperature
[77F (25C)] [
e. Battery Room Maximum Design
]F (
C)
Temperature (i.e., HVAC Failure)
[
f.
Battery Room Relative
to
%]
Humidity Range
[20 to 55%] [
]
g. Other (e.g. salt-laden air, dust)
[None] [
[Sketch No. ] [Drawing
h. Battery Room Layout
No. ] (Attachment 1)
5
|