Click here to make tpub.com your Home Page

Page Title: Terminals and connectors
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home

   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 



DOE-SPEC-3018-96
d. Where racks are shipped unassembled, number or match-mark all parts to
facilitate field assembly and provide installation instructions.
ATTENTION:
Include the following paragraph if applicable.
********************
e. Racks and rack anchorage shall be seismic rated as indicated in
paragraph 3.2.7.
3.3.5
Terminals and connectors.
a. Connectors shall meet the requirements of UL 486A or comparable standard
by any nationally recognized testing laboratory (NRTL) recognized under
29 CFR 1910.7.
b. Clearly mark each cell post for permanent identification of polarity, and seal
to the cover.
ATTENTION:
Select 15-minute rating for UPS applications, 3-hour for general-purpose.
********************
c. Provide [lead-plated copper bus bar] [
] connectors for connecting
the jars in series. All connecting [bus] [straps] and hardware shall be able to
carry the [15-minute] [3-hour] rating of the battery, or a continuous current
V] per cell,
equal to the battery's end-of-discharge voltage of [1.75 V] [
whichever provides the higher current-carrying capability. This shall be
accomplished without exceeding a temperature rise of 30C above ambient.
Provide insulated cable connectors between [tiers] [steps] and between jars
on different rack sections where the rack sections are located adjacent to
each other, or back-to-back. Arrange cable on the racks to prevent external
mechanical damage. Provide details of copper terminal connectors that are
completely lead-plated.
d. For jars mounted on the same [tier] [step] of a battery rack, provide interjar
connectors of such a length as to allow an air space of approximately
1/2 inch (13 mm) between jars.
ATTENTION:
Coodinate the selection of agent in the following paragraph with the scope of work specified in paragraphs 1.3 and
1.4.
********************
e. The [Owner will] [Seller shall] provide the cable interconnections between the
battery string (positive and negative terminals) and the battery charger. The
[Owner will] [Seller shall] also provide the inter-rack and inter-tier cabling
where rack sections are not arranged end-to-end or back-to-back. Provide
[2-hole] [4-hole] [ -hole] compression-type lead-plated connectors sized to
accommodate [Owner] [Seller] cables in sizes specified below. Provide
multi-cable terminal connections for each connection.
12


Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business