references cited herein, the text of this document takes precedence. Nothing in this
document, however, supersedes applicable laws and regulations unless a specified
exemption has been obtained.
ATTENTION:
Determine if cell jars only, or cell jars and covers shall be fire-retardant.
********************
] at the DC voltages and for the DC power system
emergency conditions] [
listed below. The batteries shall be in accordance with article 480 of NFPA 70. The
batteries shall be complete in all respects, with all required accessories. Only sealed
valve-regulated type lead-acid cells are acceptable. The cells provided shall have
fire-retardant [jars] [jars and covers] and shall be provided with flame-arrester type vents.