DOE-SPEC-3021-97
3.3.1
General. The UPS system shall consist of a UPS module and storage battery
rated to supply the requirements for the critical load as specified herein.
3.3.1.1
Source and output. The internal bypass source and the inverter
output shall be connected to the ac bus via a high-speed static
transfer switch. The static transfer switch shall automatically
transfer the ac bus to the internal bypass source only if it is available
within the tolerances noted in paragraph 3.2.2 or upon a drop in
output voltage or variation of frequency as specified in paragraph
3.3.2.1.
Power interruption interval. The power-interruption interval during
3.3.1.2
the transfer from the inverter to the internal bypass source shall not
exceed the limits defined in paragraph 3.3.5.4. If specified in
paragraph 3.3.5.2, the transfer switch shall automatically retransfer
the ac bus back to the inverter output upon restoration of normal
conditions and after a suitable time delay to avoid cycling during
slow clearing of external faults and during inrush conditions. This
transfer shall always take place for the inrush loads listed in
paragraph 3.3.5.3. A transfer in either direction shall not cause a
disturbance to the critical loads. Provide the means for the Owner
to manually inhibit automatic retransfer via the static transfer switch.
Transfer in either direction shall not cause a disturbance to the ac
load(s). Transfer shall require the inverter output to be in
synchronism with the bypass ac source, except for an inverter
failure. For inverter failure, the transfer shall complete regardless of
phase angle. The UPS module shall provide an alarm whenever a
transfer to the internal bypass source takes place. Include a
suitable time delay for this alarm to avoid alarming on momentary
transfer.
Manual transfer. Make provisions to transfer the ac bus manually to
3.3.1.3
the external maintenance bypass source for maintenance of the
static switch with a make-before-break switch for uninterrupted
transfer of power to the critical loads.
3.3.2
Inverter.
ATTENTION:
The following are guidelines for providing information about inverters, below:
The voltage regulation of most UPS systems is around 5%.
The transient response to a 100% step change in load should hold the output voltage to within 10% of
nominal and the output should recover to within 3% of nominal in 3-5 cycles.
As a guideline, the total harmonic distortion (THD) should not exceed 5%, and the maximum content of
any single harmonic should not exceed 3%.