| DOE-SPEC-3021-97
Rectifier/ Charger
Converts ac input power to dc output power for
charging the storage battery and provides power to
the inverter input.
Inverter
Converts the dc input power to a regulated and
filtered ac output power which is supplied to the
critical load.
Static Transfer Switch
Automatically transfers the critical loads, without
interruption, from the inverter output to the internal
bypass power source in the event of an inverter
problem. Also referred to as the internal bypass
switch.
Maintenance Bypass
Switch
Connects the maintenance bypass power source to
the critical loads while electrically isolating the static
switch and inverter for maintenance purposes. This
should be a make-before-break type switch.
Internal Maintenance
Bypass Switch
Connects the normal power source to the critical
loads through the static transfer switch while
electrically isolating the rectifier and inverter for
maintenance.
Storage Battery
The stored energy source which provides dc power
to the inverter input when the normal ac power to
the UPS module fails or in the event of
rectifier/charger failure.
Battery Safety Disconnect
Switch
Connects the storage battery to the rectifier. The
disconnect switch isolates the storage battery from
the UPS module for maintenance and personnel
safety.
Output Filter
Blocks high frequencies or steep wavefront
transients generated by the UPS or load from
feeding back into the load or UPS, respectively.