| DOE-SPEC-3021-97
ATTENTION:
Supply the desired source parameters for the critical loads below. The short circuit current rating should come
from the same design analysis that dictated the size of the protective circuits.
********************
UPS module output. The UPS inverter output will normally be the source of
3.2.3
supply to the uninterruptible ac bus which has the following nominal
characteristics:
Voltage
Phase/Wire
System Grounding Solid,
Ungrounded
Short Circuit Rating (amperes
rms sym. at rated voltage)
ATTENTION:
Consult with the onsite structural engineer regarding seismic requirements. Revise or delete all of
paragraph 3.2.4 as necessary. Enter the site's seismic zone using the appropriate building code.
********************
3.2.4
Seismic requirements. Equipment shall be designed for seismic zone [ ] in
accordance with [ICBO UBC.] [
.] Submit the analysis used to qualify the
UPS to be furnished for the seismic zone indicated above. Valid methods are
shown in paragraph 3.2.4.2, below.
3.2.4.1
Supports. Equipment and equipment supports shall be designed to
withstand and maintain their structural integrity when exposed to
seismic loading indicated in 3.2.4, above. The equipment structures
shall be completely self-supporting.
Demonstration of integrity. Demonstrate the equipment's ability to
3.2.4.2
withstand and maintain its structural integrity when subjected to the
forces resulting from the seismic conditions specified herein. This
shall be accomplished in one or a combination of the following
methods:
a. Predict the equipment's performance and response to a seismic
force by mathematical static analysis;
b. Test the equipment under simulated seismic conditions (static or
dynamic testing); or