|
| DOE-STD-1030-96
example, isolating a pump motor for bearing maintenance should also
include shutting and tagging the pump suction and discharge valves to
prevent possible rotation from fluid flow.
Only controlled drawings, controlled system schematics, or other
controlled documents should be used as references for determining or
verifying isolation points. In the absence of controlled drawings, a
physical walkdown should be performed by a qualified person to ensure
that isolation will be achieved by the planned lockout/tagout.
Operation or removal of tagged-out equipment is NEVER permitted.
Removal of tagged-out equipment would be impossible unless new
isolation boundaries have been established and the tagged-out component
is now itself isolated. In that case, any affected lockout/tagout should be
modified to reflect the new isolation boundaries. The obsolete tag(s)
should be removed in accordance with established procedures before
starting maintenance activities.
Some control devices "seal in" when actuated and could cause equipment
to start when power is restored. Because of this component trait, the
practice of verifying lockout/tagout isolation by operating the controls
(e.g., pressing the start button) for the affected equipment should not be
permitted.
Control switches should be tagged in a position corresponding to the
desired protective state of the equipment (e.g., OFF, neutral, pull-to-
lock), even when another device (e.g., circuit breaker, disconnect
switch, valve in pneumatic supply line) provides the primary isolation
from the energy source.
4.2.3.2 Electrical Practices
If electrical grounding devices are required, the location and sequence
for installation of each device should be specified in the lockout/tagout
procedure.
All electrical grounding devices used in a lockout/tagout should be
tagged out to ensure that the grounds remain in place until the work is
13
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |