DOE-STD-1065-94
Appendix C
SELECTED MAINTENANCE ACTIVITIES AND POSTMAINTENANCE TESTS
Maintenance Activity
Recommended Test
Perform transformer maintenance.
1.
Check transformer parameters (oil
temperature, oil level, oil pressure, tap
settings, cooling-fan status).
2.
Test transformer operability
(primary/secondary voltage and current).
3.
Check insulation resistance high-potential,
Repair (or replace) static inverters.
1.
Verify voltage and currents.
2.
Check inverter load.
3.
Perform transfer test, if applicable.
Perform electrical maintenance on
load center and distribution panel.
1.
Verify voltage and lead current.
2.
Visually check for fastener tightness,
cleanliness.
Repair cranes and hoists.
1.
Perform load test.
2.
Check limit-switch operability.
3.
Check brake/clutch operability.
Perform battery maintenance.
1.
Check battery parameters (specific gravity,
electrolyte level, cell voltage, electrolyte
temperature, battery-terminal voltage).
2.
Verify that battery cells, cell plates,
terminals, and connections are free of
corrosion.
3.
Perform battery service discharge test.
4.
Perform battery performance discharge test.