|
| DOE-STD-1066-99
14.9 Special System Guidelines
14.9.1
Water Drains
14.9.1.1
Water drains with traps and a means to eliminate drain trap evaporation
should be provided in plenum floors to provide liquid run off control.
14.9.1.2
Plenum drains should be piped to either a process waste system or to
collection tanks.
14.9.1.3
Process waste systems and collections tanks should be of sufficient
capacity to capture all liquid from the water deluge spray systems for the
densities and durations required herein.
14.9.1.4
Criticality safety should be observed in all drainage and storage systems
where the potential for impacting fissile materials is encountered.
14.9.2
Limited Water Supply Systems
14.9.2.1
Limited water supply systems for the deluge water supply should be
permitted when a documented criticality potential exists in the final filter
plenum.
14.9.2.2
A documented criticality potential should be provided showing criticality
calculations and the total amount of water allowed in the plenum enclosure
before a limited water supply system is permitted.
14.9.2.3
Limited water supply can be accomplished by either limited capacity water
tanks or system water flow control valves.
14.9.3
Maximum Air Temperatures
14.9.3.1
When normal operating temperatures of final filter enclosure are expected
to exceed 200 oF (94 oC) or when operating temperatures of the final filter
enclosure exceed the manufacturer's limited continuous service
temperature rating, a method should be provided to cool the ventilation air
stream (for filter operating temperatures see Appendix B).
14.9.3.2
Normal operating temperatures do not include high temperatures
associated with fire conditions.
14.9.3.3
High operating temperatures in the final filter enclosure can be minimized
by long runs of ducts preceding the final filter enclosure, by intake of
dilution air from streams from other spaces, or by water cooling systems
inside the ducts.
29
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |