DOE-STD-3014-96
in the analysis can be measured; however, these are only for the purpose of determining
whether further analysis should be performed. Meeting or not meeting these guidelines
should not be interpreted as indicating that preventive or mitigative actions either are or
are not required.
This standard does not include consideration of malicious acts (e.g., sabotage, terrorism,
and war). The available data on aircraft crashes do not support assessment of such acts.
Further, such acts are not unique to aircraft, nor are they initiated by failures and errors
associated with aircraft. However, the parts of this standard that address structural
response and exposure due to a release could be useful (to a limited extent) in assessing
the effects of such an assault.
Applicability. This standard is applicable to all facilities containing significant quantities of
1.3
radioactive or hazardous chemical materials. For the purposes of this standard, a facility
contains significant quantities of such material if it meets one or more of the following
conditions:
a.
The facility contains radioactive material, and the inventory of such material would
cause the facility to be classified as a Hazard Category 1 or Hazard Category 2
facility in accordance with the criteria established by the U.S. Department of
Energy (DOE) (Reference 1); or
b.
The facility contains hazardous chemicals in quantities that make it subject to the
requirements of 29 Code of Federal Regulations (CFR) 1910.119 (Reference 2); or
c.
The facility contains hazardous chemicals that make it subject to the requirements
of the Environmental Protection Agency's (EPA's) Risk Management Program
The conditions above specify the minimum circumstances under which this standard
should apply. However, they do not preclude applying this standard or its parts to facilities
that do not meet any of these conditions. Users are encouraged to consider whether there
are special circumstances in which a particular facility should be subject to this standard