DOE-STD-3020-97
5.0
HEPA FILTER PROCUREMENT
5.1
General
HEPA filters to be installed in facilities operated under contract to DOE shall
be purchased in compliance with the specifications of this standard. The
purchaser shall provide the FTF manager a copy of the purchase order,
including any non-standard requirements for the filter product, as a means to
assure that the purchase order includes proper specifications, and that the
vendor meets the stipulations of the purchase order. Disagreements on the
specification content, or changes thereto, shall be resolved in writing by the
purchaser and the FTF manager.
5.2
Performance Requirements
Mandatory performance requirements for HEPA filters are set out below.
These performance requirements must be demonstrated by test or
inspection by manufacturer and FTF.
Penetration. Aerosol penetration for any HEPA filter shall not exceed
5.2.1
0.03% (0.0003) at 0.3 micrometer diameter particles.
Resistance. Air flow resistance across the HEPA filter shall conform
5.2.2
to the limits listed in Table 1 below. Tests for resistance to airflow
shall be conducted at flow rates expressed in actual cubic feet per
minute (ACFM).
5.2.3
Media Velocity (Effective Media Area). The total effective media area
provided within the filter pack shall be such that face velocity shall not
exceed 5.0 ft/min (1.52 m/min) at the rated air flow.