| DOE-STD-3025-99
APPENDIX 1- QUALIFICATION OF NEW TEST METHODS AND EQUIPMENT
1.1
SPECIFICATIONS
Only test equipment and measurement techniques approved by the DOE shall be used for quality
assurance testing of HEPA filters at the FTFs. DOE approval shall be contingent on satisfactory
completion of the following specifications.
1.2
PARTICLE SIZE
1.2.1
Particle Size Range
The new instrument and/or test technique shall be capable of determining aerosol
penetration in the particle diameter ranged from 0.1 micrometers to greater than 0.3
micrometers in discrete measurable particle size ranges no larger than 0.05 Fm.
Particle size measurements shall have a precision and accuracy of 10%.
1.3
1.3.1
Measurement Capability
The new instrument and/or test technique shall be capable of measuring airflow
resistance within an accuracy and precision of 5% of a filter under test at its nominal
airflow rating.
1.3.2
Pressure and temperature measuring instruments, orifice plates, mass-flow meters and
other instruments critical to performance of the proposed test technique shall be
calibrated by the use of standards traceable to recognizable NIST standards.
1.4
PENETRATION
1.4.1
Penetration Measurement
The test method shall be capable of determining penetration up to 0.03% +0.005% in
the particle diameter range from 0.1 Fm to 0.2 Fm. Aerosol dilution will be permitted
only after demonstration that the overall test efficiency and reliability have not been
adversely affected, nor have the dilution techniques adversely affected particle size or
concentration.
17
|