| DOE-HDBK-1106-97
Lesson Plan
Instructor's Notes
F. Release of Materials
1. Release to Controlled Areas
Insert facility-specific
Release from potentially contaminated areas to
information as appropriate (if
Controlled Areas is covered by 10 CFR 835.
laboratory personnel do not
conduct release surveys, it
Equipment and materials released from a potentially
may be appropriate to just
contaminated area must be surveyed and released under
cover their responsibilities).
a formal program.
Reference: DOE/CH-9401
If surveys indicate the presence of removable
(1993)
contamination at levels greater than 10 CFR 835
Appendix D, the materials may be moved to another
Reference: 10 CFR
posted area. Appropriate controls must be
835.1101(b)
established and should include:
Surveys of materials before movement.
Containment of materials during transit.
Establishment of approved transit routes.
Survey of transit route after movement (if materials
exhibited removable contamination).