| DOE-STD-3020-2005
Qualification testing of a filter listed in Table 5.1 qualifies all filters with a lower
flow rate, which have similar construction except:
The size 4 filters shall be qualified separately.
The size 2 filters cannot qualify a size 1 filter.
For qualification testing of special HEPA filters described in Section 5.5, refer
to ASME AG-1, FK-5000.
DOE reserves the right to randomly select HEPA filters from existing storage
at DOE sites and perform the tests defined in Section 6.1.2. If failures are
noted, the manufacturer, the FTF, and DOE contractor procurement
specialists shall be informed that the failed filter model is no longer acceptable
for use in DOE facilities, pending requalification.
6.1.2
Qualification Testing: Qualification tests of filter components shall be
conducted in accordance with requirements of ASME AG-1, FC-5000 or
FK-5000. Filters selected for qualification testing may be prototypes of the
proposed design or production filters of the specific design randomly selected
from the manufacturer's stock as long as they have been manufactured using
the same method, material, equipment and processes as will be used during
regular production. The number of filter units required for qualification testing
shall be as specified in ASME AG-1.
6.1.3
Production Testing: The manufacturer shall perform production tests for
each filter manufactured in accordance with Section 5.0. The results of the
penetration and resistance tests shall be documented and identified by serial
number for each individual filter unit.
6.1.4
HEPA Filter Labeling: HEPA filters and shipping containers shall be
labeled as specified in ASME AG-1, FC-9000. In addition, the label shall
include the date of the tests and the effective filter media area.
6.2
DOE Quality Assurance Testing, Inspection and Labeling:
6.2.1
Quality Assurance Inspection and Testing: Those filters specified in
Section 4 requiring a FTF Quality Assurance test shall be tested at a DOE
designated FTF. Acceptance is contingent upon satisfactory completion of
inspections and tests specified in DOE Standards. Filters will be inspected
for physical damage to the packaging and filter, and for compliance with
specification requirements which can be checked visually. Each filter shall be
tested for penetration and resistance in accordance with the tests specified in
Section 6.1.3. The penetration at each specified airflow and the resistance at
17
|